Power allocator governor tunables |
|
================================= |
|
|
|
Trip points |
|
----------- |
|
|
|
The governor works optimally with the following two passive trip points: |
|
|
|
1. "switch on" trip point: temperature above which the governor |
|
control loop starts operating. This is the first passive trip |
|
point of the thermal zone. |
|
|
|
2. "desired temperature" trip point: it should be higher than the |
|
"switch on" trip point. This the target temperature the governor |
|
is controlling for. This is the last passive trip point of the |
|
thermal zone. |
|
|
|
PID Controller |
|
-------------- |
|
|
|
The power allocator governor implements a |
|
Proportional-Integral-Derivative controller (PID controller) with |
|
temperature as the control input and power as the controlled output: |
|
|
|
P_max = k_p * e + k_i * err_integral + k_d * diff_err + sustainable_power |
|
|
|
where |
|
- e = desired_temperature - current_temperature |
|
- err_integral is the sum of previous errors |
|
- diff_err = e - previous_error |
|
|
|
It is similar to the one depicted below:: |
|
|
|
k_d |
|
| |
|
current_temp | |
|
| v |
|
| +----------+ +---+ |
|
| +----->| diff_err |-->| X |------+ |
|
| | +----------+ +---+ | |
|
| | | tdp actor |
|
| | k_i | | get_requested_power() |
|
| | | | | | | |
|
| | | | | | | ... |
|
v | v v v v v |
|
+---+ | +-------+ +---+ +---+ +---+ +----------+ |
|
| S |-----+----->| sum e |----->| X |--->| S |-->| S |-->|power | |
|
+---+ | +-------+ +---+ +---+ +---+ |allocation| |
|
^ | ^ +----------+ |
|
| | | | | |
|
| | +---+ | | | |
|
| +------->| X |-------------------+ v v |
|
| +---+ granted performance |
|
desired_temperature ^ |
|
| |
|
| |
|
k_po/k_pu |
|
|
|
Sustainable power |
|
----------------- |
|
|
|
An estimate of the sustainable dissipatable power (in mW) should be |
|
provided while registering the thermal zone. This estimates the |
|
sustained power that can be dissipated at the desired control |
|
temperature. This is the maximum sustained power for allocation at |
|
the desired maximum temperature. The actual sustained power can vary |
|
for a number of reasons. The closed loop controller will take care of |
|
variations such as environmental conditions, and some factors related |
|
to the speed-grade of the silicon. `sustainable_power` is therefore |
|
simply an estimate, and may be tuned to affect the aggressiveness of |
|
the thermal ramp. For reference, the sustainable power of a 4" phone |
|
is typically 2000mW, while on a 10" tablet is around 4500mW (may vary |
|
depending on screen size). It is possible to have the power value |
|
expressed in an abstract scale. The sustained power should be aligned |
|
to the scale used by the related cooling devices. |
|
|
|
If you are using device tree, do add it as a property of the |
|
thermal-zone. For example:: |
|
|
|
thermal-zones { |
|
soc_thermal { |
|
polling-delay = <1000>; |
|
polling-delay-passive = <100>; |
|
sustainable-power = <2500>; |
|
... |
|
|
|
Instead, if the thermal zone is registered from the platform code, pass a |
|
`thermal_zone_params` that has a `sustainable_power`. If no |
|
`thermal_zone_params` were being passed, then something like below |
|
will suffice:: |
|
|
|
static const struct thermal_zone_params tz_params = { |
|
.sustainable_power = 3500, |
|
}; |
|
|
|
and then pass `tz_params` as the 5th parameter to |
|
`thermal_zone_device_register()` |
|
|
|
k_po and k_pu |
|
------------- |
|
|
|
The implementation of the PID controller in the power allocator |
|
thermal governor allows the configuration of two proportional term |
|
constants: `k_po` and `k_pu`. `k_po` is the proportional term |
|
constant during temperature overshoot periods (current temperature is |
|
above "desired temperature" trip point). Conversely, `k_pu` is the |
|
proportional term constant during temperature undershoot periods |
|
(current temperature below "desired temperature" trip point). |
|
|
|
These controls are intended as the primary mechanism for configuring |
|
the permitted thermal "ramp" of the system. For instance, a lower |
|
`k_pu` value will provide a slower ramp, at the cost of capping |
|
available capacity at a low temperature. On the other hand, a high |
|
value of `k_pu` will result in the governor granting very high power |
|
while temperature is low, and may lead to temperature overshooting. |
|
|
|
The default value for `k_pu` is:: |
|
|
|
2 * sustainable_power / (desired_temperature - switch_on_temp) |
|
|
|
This means that at `switch_on_temp` the output of the controller's |
|
proportional term will be 2 * `sustainable_power`. The default value |
|
for `k_po` is:: |
|
|
|
sustainable_power / (desired_temperature - switch_on_temp) |
|
|
|
Focusing on the proportional and feed forward values of the PID |
|
controller equation we have:: |
|
|
|
P_max = k_p * e + sustainable_power |
|
|
|
The proportional term is proportional to the difference between the |
|
desired temperature and the current one. When the current temperature |
|
is the desired one, then the proportional component is zero and |
|
`P_max` = `sustainable_power`. That is, the system should operate in |
|
thermal equilibrium under constant load. `sustainable_power` is only |
|
an estimate, which is the reason for closed-loop control such as this. |
|
|
|
Expanding `k_pu` we get:: |
|
|
|
P_max = 2 * sustainable_power * (T_set - T) / (T_set - T_on) + |
|
sustainable_power |
|
|
|
where: |
|
|
|
- T_set is the desired temperature |
|
- T is the current temperature |
|
- T_on is the switch on temperature |
|
|
|
When the current temperature is the switch_on temperature, the above |
|
formula becomes:: |
|
|
|
P_max = 2 * sustainable_power * (T_set - T_on) / (T_set - T_on) + |
|
sustainable_power = 2 * sustainable_power + sustainable_power = |
|
3 * sustainable_power |
|
|
|
Therefore, the proportional term alone linearly decreases power from |
|
3 * `sustainable_power` to `sustainable_power` as the temperature |
|
rises from the switch on temperature to the desired temperature. |
|
|
|
k_i and integral_cutoff |
|
----------------------- |
|
|
|
`k_i` configures the PID loop's integral term constant. This term |
|
allows the PID controller to compensate for long term drift and for |
|
the quantized nature of the output control: cooling devices can't set |
|
the exact power that the governor requests. When the temperature |
|
error is below `integral_cutoff`, errors are accumulated in the |
|
integral term. This term is then multiplied by `k_i` and the result |
|
added to the output of the controller. Typically `k_i` is set low (1 |
|
or 2) and `integral_cutoff` is 0. |
|
|
|
k_d |
|
--- |
|
|
|
`k_d` configures the PID loop's derivative term constant. It's |
|
recommended to leave it as the default: 0. |
|
|
|
Cooling device power API |
|
======================== |
|
|
|
Cooling devices controlled by this governor must supply the additional |
|
"power" API in their `cooling_device_ops`. It consists on three ops: |
|
|
|
1. :: |
|
|
|
int get_requested_power(struct thermal_cooling_device *cdev, |
|
struct thermal_zone_device *tz, u32 *power); |
|
|
|
|
|
@cdev: |
|
The `struct thermal_cooling_device` pointer |
|
@tz: |
|
thermal zone in which we are currently operating |
|
@power: |
|
pointer in which to store the calculated power |
|
|
|
`get_requested_power()` calculates the power requested by the device |
|
in milliwatts and stores it in @power . It should return 0 on |
|
success, -E* on failure. This is currently used by the power |
|
allocator governor to calculate how much power to give to each cooling |
|
device. |
|
|
|
2. :: |
|
|
|
int state2power(struct thermal_cooling_device *cdev, struct |
|
thermal_zone_device *tz, unsigned long state, |
|
u32 *power); |
|
|
|
@cdev: |
|
The `struct thermal_cooling_device` pointer |
|
@tz: |
|
thermal zone in which we are currently operating |
|
@state: |
|
A cooling device state |
|
@power: |
|
pointer in which to store the equivalent power |
|
|
|
Convert cooling device state @state into power consumption in |
|
milliwatts and store it in @power. It should return 0 on success, -E* |
|
on failure. This is currently used by thermal core to calculate the |
|
maximum power that an actor can consume. |
|
|
|
3. :: |
|
|
|
int power2state(struct thermal_cooling_device *cdev, u32 power, |
|
unsigned long *state); |
|
|
|
@cdev: |
|
The `struct thermal_cooling_device` pointer |
|
@power: |
|
power in milliwatts |
|
@state: |
|
pointer in which to store the resulting state |
|
|
|
Calculate a cooling device state that would make the device consume at |
|
most @power mW and store it in @state. It should return 0 on success, |
|
-E* on failure. This is currently used by the thermal core to convert |
|
a given power set by the power allocator governor to a state that the |
|
cooling device can set. It is a function because this conversion may |
|
depend on external factors that may change so this function should the |
|
best conversion given "current circumstances". |
|
|
|
Cooling device weights |
|
---------------------- |
|
|
|
Weights are a mechanism to bias the allocation among cooling |
|
devices. They express the relative power efficiency of different |
|
cooling devices. Higher weight can be used to express higher power |
|
efficiency. Weighting is relative such that if each cooling device |
|
has a weight of one they are considered equal. This is particularly |
|
useful in heterogeneous systems where two cooling devices may perform |
|
the same kind of compute, but with different efficiency. For example, |
|
a system with two different types of processors. |
|
|
|
If the thermal zone is registered using |
|
`thermal_zone_device_register()` (i.e., platform code), then weights |
|
are passed as part of the thermal zone's `thermal_bind_parameters`. |
|
If the platform is registered using device tree, then they are passed |
|
as the `contribution` property of each map in the `cooling-maps` node. |
|
|
|
Limitations of the power allocator governor |
|
=========================================== |
|
|
|
The power allocator governor's PID controller works best if there is a |
|
periodic tick. If you have a driver that calls |
|
`thermal_zone_device_update()` (or anything that ends up calling the |
|
governor's `throttle()` function) repetitively, the governor response |
|
won't be very good. Note that this is not particular to this |
|
governor, step-wise will also misbehave if you call its throttle() |
|
faster than the normal thermal framework tick (due to interrupts for |
|
example) as it will overreact. |
|
|
|
Energy Model requirements |
|
========================= |
|
|
|
Another important thing is the consistent scale of the power values |
|
provided by the cooling devices. All of the cooling devices in a single |
|
thermal zone should have power values reported either in milli-Watts |
|
or scaled to the same 'abstract scale'.
|
|
|